6 - Technical specification
Features
(at 25°C enviromental temp.)
Setpoint
OP4 PV retransmission
(option)
One shot Fuzzy-Tuning
with automatic selection
Serial comm. (option)
Auxiliary Supply
Operational safety
General
characteristics
Description
Ramp up and down
Low limit
High limit
Galvanic isolation
: 500 V
~/1 min
Resolution 12bit (0.025%)
Accuracy
: 0.1 %
The controller selects automatically the best
method according to the process conditions
Natural frequency
Step response
Current output: 0/4…20mA 750/15V max
From low limit to the high range
From low range to the high limit
0.1…999.9 digit/min (Off = 0)
RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/sec 2 wires
Electromagnetic
compatibility
Access protection
Power supply
Protection EN650529
Compliance to the CE standards for industrial system and equipment
Electric safety
IP20 termination unit
IP65 front panel
+18V– ±20%, 30mA max for an external transmitter supply
Password to access the configuration and parameters data
100 - 240V
~ (- 15% + 10%) 50/60Hz
or 24V~ (- 25% + 12%) 50/60Hz and 24V– (- 15% + 25%)
Power consumption 1.6W max
Compliance to EN61010, installation class 2 (2500V) pollution class 2
Detection of out of range, short circuit or sensor break with automatic
activation of the safety strategies and alerts on display
Dimensions
Safety value: 0…+100%. (user enabled/disabled)
parameter and configuration data are stored in a non volatile memory for
an unlimited time
Measure input
1
/
32
DIN - 48 x 24, depth 120 mm, weight 100 gr. apx.
Control output
Parameters
UL, cUL