Athena Technologies C10 Satellite Radio User Manual


 
27
4 - Operations
Note
Pressing the Q the next group of
parameters is displayed.
[1] Table of the supported Engineering
Units.
* For inputs from thermocouple or resistance
thermometer, the choice is between °C and
°F only.
[2] Range of min 100 digits.
[3] If password is 0000 to 4999, parameter set-
ting will be available to the operator with-
out entering this password number. If pass-
word is 5000 to 9999, parameter setting
will only be available by entering this pass-
word number.
Centigrade degrees *
°C
Fahrenheit degrees *
°f
none
none
mV
nU
Volt
U
mA
MA
Ampere
A
Bar
bAr
PSI
psI
Rh
rh
pH
ph
2002
I L M N
OK
pAsstune
Conf
sc.d.d
33
Unit
2nd GROUP
Engineering
units
(see table)
N° of decimals
(linear scale only)
0…3
Entry of digits
I-L-M-N
of the
configuration
code
(chapter 3.2
page 16)
Code entry [3]
from 0 to 4999
(33 default from factory)
The entered password must
correspond to the one store
in the Code parameter.
A
If the controller has not been
configured
Conf is shown on
the front panel at the power up.
In this situation, the controller has
its outputs and inputs not active.
This situation ends when a correct
configuration code is entered.
Password entry [3]
only if
Code
value <5000
YES
NO