Commissioning Radar Tank Gauge
62 Installation and Operations Manual
manual
The value pairs in the dip table can be read and written. You can enter the measured
value and the dip value.
–uncorrected measured value:
This is the measured value supplied by the instrument, NOT corrected by the dip
table. The choice of measured value, level or remaining fill height is dependent on
the instrument setting.
–Dip value:
This is the level or distance to flange respectively, given by the hand dip. This value
should be used to correct the measured value.
The "manual mode" of the dip table can be used to enter collected data after a series
of data pairs taken at different tank levels.
Note!
The bigger the distance between the different levels while taking hand dips, the more
accurate the linearization of the dip table will be.
semi-automatic
The value pairs in the dip table can be read. You can enter the dip value only. When there
are new value pairs, the current level or distance is accepted as the measured value.
table on
The dip table is switched on.
table off
The dip table is switched off.
clear table
The complete dip table is deleted. The table is switched off. The number of free table
entries is set to the maximum value (=32).
View
The value pairs in the dip table can only be read. You can still select this menu option,
even if there is no dip table available. In this case, the number of free table entries is at
maximum value (=32).
Function "dip table" (034)
This function edits measured variable. The number behind the entry "remain" indicates
the current number of remaining free value pairs. The maximum number of value pairs
is 32; after each entry, the remaining number is decremented.
Note!
The uncorrected measured value is displayed in the "dip table" (034) function. This may
differ considerably from the measured values when a dip table is activated.
Function "dip table" (035)
This function edits the dip value.
⇒
E
+
–
⇒
E
+
–