Performance Under Rated Conditions * - Model STR17G (0-100 to 0-3000 psig)
Parameter Description
Upper Range Limit ** psig
bar
3000
210
Minimum Span psig
bar
100
7
Turndown Ratio
30 to 1
Zero Elevation and Suppression
No limit except minimum span from absolute zero to 100% of URL. Specifications valid
over this range.
Accuracy (Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)
•
Accuracy includes residual error
after averaging successive
readings.
• For FOUNDATION Fieldbus use
Digital Mode specifications. For
HART use Analog Mode
specifications.
In Analog Mode:
±0.15% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (300 psi), accuracy equals:
±0.10 + 0.05
()
300 psi
span psi
or ±0.10 + 0.05
()
21 bar
span bar
in % of span
In Digital Mode: ±0.125% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (300 psi), accuracy equals:
±0.075 + 0.05
()
300 psi
span psi
or ±0.075 + 0.05
()
21 bar
span bar
in % of span
* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
** Transmitter URL limit or maximum seal pressure rating, whichever is lower.