Performance Under Rated Conditions * - Model STR14A (0-5 to 0-500 psia)
Parameter Description
Upper Range Limit ** psia
bar absolute
500
35
Minimum Span psia
bar absolute
5
0.35
Turndown Ratio
100 to 1
Zero Elevation and Suppression
No limit except minimum span from 0 to 100% URL.
Accuracy (Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)
Accuracy includes residual error
after averaging successive
readings.
For FOUNDATION Fieldbus use
Digital Mode specifications. For
HART use Analog Mode
specifications.
In Analog Mode:
±0.1% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (20 psi), accuracy equals:
±0.05 + 0.05
()
20 psi
span psi
or ±0.05 + 0.05
()
1.4 bar
span bar
in % of span
In Digital Mode: ±0.075% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (20 psi), accuracy equals:
±0.025 + 0.05
()
20 psi
span psi
or ±0.025 + 0.05
()
1.4 bar
span bar
in % of span
* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
** Transmitter URL limit or maximum seal pressure rating, whichever is lower.
Performance Under Rated Conditions – General for all Models
Parameter Description
Output (two-wire)
Analog 4 to 20 mA or digital communications DE mode. Options available for
F
OUNDATION Fieldbus and HART protocol.
Supply Voltage Effect
±0.005% of span per volt.
Damping Time Constant
Adjustable from 0 to 32 seconds digital damping.
RFI Protection (Standard)
Negligible (20 to 1000 MHz at 30 volts per meter).
CE Conformity (Europe)
89/336/EEC, Electromagnetic Compatibility (EMC) Directive.
NAMUR NE 43 Compliance
Option
Transmitter failure information is generated when the measuring information is invalid or
no longer present. Failure information is transmitted as a current signal but outside the
normal 4-20 mA measurement signal level. Transmitter failure values are: 3.6 mA and
21.0 mA. The normal signal range is 3.8 mA and 20.5 mA.
SIL 2/3 Compliance
SIL certified to IEC 61508 for non-redundant use in SIL 2 related Safety Systems
(single use) and for redundant (multiple) use in SIL 3 Safety Systems through
TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 1998;
IEC 61508-2: 2000; IEC61508-3: 1998.