Performance Under Rated Conditions * - Model STR14G (0-5 to 0-500 psig)
Parameter Description
Upper Range Limit ** psig
bar
500
35
Minimum Span psig
bar
5
0.35
Turndown Ratio
100 to 1
Zero Elevation and Suppression
No limit except minimum span from absolute zero to 100% of URL. Specifications valid
over this range.
Accuracy (Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)
•
Accuracy includes residual error
after averaging successive
readings.
• For FOUNDATION Fieldbus use
Digital Mode specifications. For
HART use Analog Mode
specifications.
In Analog Mode:
±0.1% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (20 psi), accuracy equals:
±0.05 + 0.05
()
20 psi
span psi
or ±0.05 + 0.05
()
1.4 bar
span bar
in % of span
In Digital Mode: ±0.075% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (20 psi), accuracy equals:
±0.025 + 0.05
()
20 psi
span psi
or ±0.025 + 0.05
()
1.4 bar
span bar
in % of span
* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
** Transmitter URL limit or maximum seal pressure rating, whichever is lower.