![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/d/b5/db5806c4-680d-4c73-953e-55d5beb56675/db5806c4-680d-4c73-953e-55d5beb56675-bg1d.png)
Web/SNMP Management SmartSlot Card User’s Guide 29
Network Menu
Option Settings
continued
SNMP
An
Access
option (the
Settings
option in the Control Console) enables
(by default) or disables SNMP. When SNMP is enabled, the
Access
Control
settings allow you to control how each of the four available
SNMP channels is used.
Note:
For information about how to define up to four
NMS
s which will
server as trap receivers, see
Trap receivers on page 55
; for
more information about how to use SNMP to manage a UPS or
an Environmental Monitoring SmartSlot Card, see the
PowerNet MIB Reference Guide on the APC Web/SNMP
Management Card utility CD (.\doc\mibguide.pdf).
Setting Definition
Community
Name
This setting defines the password (maximum of 15 characters)
which an NMS that is defined by the
NMS IP
setting below uses to
access the channel.
NMS IP
Limits access to the NMS or NMSs specified by the format used for
the IP address. For example:
•
159.215.12.1
allows only the NMS with that specific IP address to
have access.
•
159.215.12.255
allows access for any NMS on the 159.215.12
segment.
•
159.215.255.255
allows access for any NMS on the 159.215
segment.
•
159.255.255.255
allows access for any NMS on the 159 segment.
•
0.0.0.0
or
255.255.255.255
allows access for any NMS.
Access Type
Selects how the
NMS
defined by the
NMS IP
setting can use the
channel, when that
NMS
uses the correct
Community Name
.
Read
The
NMS
can use
GET
s at any time, but it can never
use
SET
s.
Write
The
NMS
can use
GET
s at any time, and can use
SET
s
when no one is logged into either the Control Console
or Web interface.
Write+
The
NMS
can use
GET
s and
SET
s at any time.
Disabled
The NMS cannot use
GET
s or
SET
s.