Specifications: 40 kW InfraStruXure PDU
InfraStruXure System - Installation and Start-Up 43
.
Configuration Delta to WYE
Maximum Power Rating 60kVA
Maximum Current Rating 166A 72A 58A
Construction Cu windings, open core
Temperature Rating 220° C (Class H)
Maximum Temperature Rise 150°C
Efficiency 97–98%
Environmental
Operating Environment Protected from water and conductive contaminates
Temperature
Operating 32 to 104° F (0 to 40° C)
Storage 32 to 113° F (0 to 45° C)
Class Class H (220° C)
Humidity
Operating 0 to 95%, non-condensing
Storage 0 to 95%, non-condensing
Elevation
Storage 3,000 ft (10 000 m)
Acoustic Noise Emission Maximum 50dB(A) at 1 m
Heat Rejection at Full Load 5194 BTU/hr. (1.5 kW)
Compliance
Approvals UL 60950, cUL
†Transformerless units only.
†† Provided by customer.
‡ The specifications are recommendations. Consult the NEC and local codes for requirements
specific to your installation.
Physical PD40F6FK1-M PD40G6FK1-M PD40L6FK1-M