InfraStruXure System - Installation and Start-Up 41
Specifications
40 kW InfraStruXure PDU
Electrical PD40F6FK1-M PD40G6FK1-M PD40L6FK1-M
Input
Nominal Voltage Requirements 208/120 V 480/277 V 600/346 V
Nominal Current 125 A 54 A 43 A
Frequency 57–63 Hz 57–63 Hz 57–63 Hz
Voltage Configuration
Transformer 3W + G + GEC
Without Transformer 4W + G
Upstream Circuit Breaker
††
175 AT 80 AT 60 AT
Main Input Conductor Size
3/0 AWG #3 AWG #4 AWG
UPS Breaker Size 175 AT 175 AT 175 AT
Maximum Continuous Current 155 A 67 A 54 A
Grounding PE node (from AC or floor grid)
Output
Voltage AC 3-phase 4-wire PE
Nominal Voltage 208:120 V WYE
UPS Breaker Size 150 AT 150 AT 150 AT
Max. Distribution Breaker Size 150 AT 150 AT 150 AT
Number of Distribution Panels 2 × 225A, 42- position
Full Load Rating 40 kW 40 kW 40 kW
Max. Contin Current + 125% overload 139 A 139 A 139 A
Nominal Current 111 A 111 A 111 A
Internal Static Switch Fuses
175 A
Over-current Protection
PDU Current Determined by UPS
Grounding Separately derived neutral/ground bond
Wiring
UPS to PDU 3W + G (1/0 AWG)
PDU to Distribution Panels 4W + G (1/0 AWG)
Distribution Panels to Racks/Power Strips 4W + G (12 AWG)
Power Cable Connections L21-20 connector system