When the engine starts, a permanent magnet implanted in the rotor rotates, creating voltage in
the main coil (MC). When a load makes contact with the coil, the load current passing through
the primary coil of current transformer causes a magnetizing current to flow in ratio to the load
current flowing through the current transformer primary coil. This magnetizing current passing
through a diode to field coil creates a strong magnetic field in the rotor which falls with the
amount of the load, increasing the voltage.
G
r
iENERATOR
CONTROL BOX
___--- ------
ir
__--- -__-__-__-__-__---------
AC output
1
terminal !
0’
ll:
4-3-4 THE ADVANTAGES OF CURRENT TRANSFORMER CONTROL (RGV13000T)
With AVR control, control is effected according to variations in output voltage.
When an inductive load is applied, a large starting current is required (current variations are
greater than voltage variation), precise control becomes difficult.
Current transformer control, on the other hand, controls the output voltage according to the
load current, which is better for using inductive load.
- 17-