Subaru Robin Power Products 13OOOT Cassette Player User Manual


 
If the RESET button pops out during operation, stop the generator immediately and call
a qualified electrician for checking generator and the appliances.
(2) CONNECTING TO DOMESTIC CIRCUIT (HOUSE WIRING)
All Robin generators are a neutral ungrounded type.
If a generator is to be connected to residential or commercial power lines, such as a
stand-by power source during power outage, all connections must be made by a
licensed electrician.
Failure in connection may result in death, personal injury, damage to generator, dam-
age to appliances, damage to the building’s wiring or fire.
(a) When connecting a Robin generator to a house wiring, generator output power must be taken
from the 24OV-4P receptacle.
(b) Install a transfer switch.
A transfer switch must be installed to transfer the load from the commercial power source to
the generator. This switch is necessary to prevent accidents caused by the recovery from
power outage. Use a transfer switch of the correct capacity.
Install transfer switch between the meter and the fuse or AC breaker box.
[CAUTION]
If the neutral wire of house wiring is grounded, be sure to ground the ground terminal
of the generator, Otherwise an electric shock may occur to the operator.
- 13-