Check the amperage of the receptacles used referring to
TABLE 1,
and be sure not to take a
current exceeding the specified amperage.
n
Be sure that the total wattage of all appliances dose not exceed the rated output of the gen-
erator.
Style
Ampere
up
to20A
Receptacle
AC plug
NEMA NEMA
5-20R 5-2OP
Description
GFCI (Ground Fault Circuit
interrupter) Receptacle, duplex
(RECl)
up to 30A
up to 30A
up to 50A
NEMA
L!5-30R
NEMA
L14-30R
NEMA Locking Receptacle
L5-30 P
(REC2)
NEMA
Locking Receptacle
L143OP
(REC3)
Locking Receptacle (REC4)
TABLE 1
NOTE :
When the no-fuse breaker turns off during operation, the generator is over loaded or the appli-
ance is defective. Stop the generator immediately, check the appliance and / or generator for
overloading or detect and have repaired as necessary by Robin dealer or service shop.
-[CAUTION]
The duplex 120V receptacle is protected by a GFCI (Ground Fault Circuit Interrupter).
GFCI shuts off the output current from the duplex 120V receptacle when a ground fault
occurs in the generator or the appliance.
Please note that other receptacles are not protected by GFCI.
GFCI RECEPTACLE
After starting the engine, check the GFCI for proper functioning by the following test procedure.
n
Push yellow TEST button, The red RESET button will pop out exposing the word TRIP.
Power is now off at the outlets protected by the GFCI, indicating that the device is functioning
properly.
m If TRIP dose not appear when testing, do not use the generator. Call a qualified electrician.
n
To restore power, push RESET button.