Emerson Process Management MSP-ULOG1 Satellite Radio User Manual


 
(IP2042/QS) January 2006 6
Application/Duty: Flow Measurement
1. With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCULOG unit (see previous pages), you
can now programme the MCULOG for an application. This application example is for flow measurements.
Requirement
Live flow measurements in units of cubic metres per second.
Totalised flow in cubic metres per second.
Input Data
Channel Shape: Flume
Maximum depth: 1 metre
Maximum rate: 1 cubic metre per second
The MSP900SH transmitter is supplying live level measurements in units of
metres.
Output Data
The MCULOG will be calculating the flow rate.
Logging
See pages 8/9.
4. Work through the “Duty” Wizard prompts until completion; this occurs when the menu system re-appears. Keypad
hints, for the illustrated Wizard sequence on the next page, are provided alongside the prompts. If applicable, adapt
the example to suit your application.
5. Circled numbers in the illustrated Wizard sequence relate to these notes:
c Select “Flow” from the multiple-choice list.
d Enter the maximum rate of flow.
e Enter the present height of maximum flow in the Flume.
f Option of registering flow as 0 m
3
/s on the MCULOG while the measured flow rate is below a programmed cut off.
g Programme the 4-20mA output span with a flow rate range (e.g. 0 m
3
/s to 1 m
3
/s)
h Option to set-up a relay to output (100ms) pulses representing the totalised flow.
6. Return to the main menu by holding the ESC key for a few seconds, releasing it when the main menu appears. Next, go
on-line by selecting the “Go on-line” menu option and then pressing the ENTER key once. Finally, press the ESC key
repeatedly until the primary display appears. The flow measurement will be live on the primary display.
2. Navigate the menu system to get to the “Duty Wizard”
screen. Key-press hints are alongside the screens.
3. Start the “Duty” Wizard by pressing the yellow (ENTER) key once.