Post DBE Operation
Accuracy at reference conditions shall be within ±2.5% of upper range limit
(±3.75% for Range Code 0) for one year following DBE.
Quality Assurance Program
In accordance with NQA-1, 10CFR50 Appendix B, and ISO 9001:2000
Nuclear Cleaning
To 1 ppm maximum chloride content
Hydrostatic Testing
To 150% of maximum working pressure or 2,000 psi (13.8 MPA), whichever is
greater
Traceability
In accordance with NQA-1, 10CFR50 Appendix B; chemical and physical
material certification of pressure-retaining parts
Qualified Life
The transmitter qualified life is dependent on continuous ambient temperature
at the installation site (see Figure 6-1). Replacement of amplifier and
calibration circuit boards at the end of their qualified life permits extension of
the transmitter qualified life to the module qualified life. See Rosemount
Report D8400102 for details.
Figure 6-1. Qualified Life vs.
Ambient Temperature.
PERFORMANCE
SPECIFICATIONS
Based on zero-based ranges under reference conditions.
Accuracy
±0.25% of calibrated span; includes combined effects of linearity, hysteresis,
and repeatability
Dead Band
None
Electronics
Qualified Life
Temperature (°F)
Time (Years)
Module
Qualified Life