5. Install
Chassis
Ground
Connections
Ground
Strips
Attach ribbon cables between
LonWorks control card and memory
card.
Be sure exposed wire portion of ribbon
cable (A) is facing front of socket (B).
Do not remove blue insulation covering
end of ribbon cable.
Pull up collar (C) of ribbon cable socket,
insert cable and push collar closed.
Repeat procedure for all ribbon cables.
Remove terminal connector from
terminal block (D) and connect to
terminal block (E) at this time for ease
of access.
6. Install
Ribbon
Cables
between
Option
Cards
(D)
(E)
Align ground strips over pre-tapped
screw holes provided. Tabs on
grounding strips point toward outside of
chassis.
Replace screws removed in step 4 and
add additional screws and washers
provided, as necessary. Tighten to
8 in-lbs using Torx T-20 screw driver.