Index
No.
Name Description Valid Range Initial Value Permission
35 INTERNAL_ALERTS Bad position sensor N/A Read only
Bad temperature sensor
System temperature exceeded
Software error IO card
Travel deviation alert
Device shutdown
Unknown error
41 RECOMMENDED_ACTION Enumerated list of recommended actions of the device,
displayed with a device alert (can be multiple, see table
below)
N/A 0 Read only
see table
42 FAILED_PRI Designates the alarming priority of the FAILED_ALM.
Handling defined by FF.
0: All FAILED alerts disabled
1: All failed alerts supressed
2: Higher process failed alerts
0 to 15 2 Read / Write
43 FAILED_ENABLE see alert table N/A
44 FAILED_MASK see alert table
45 FAILED_ACTIVE see alert table N/A Read only
46 FAILED_ALM Alarm indicating a failure within a device which makes the
device non-operational.
UNACKNOWLEDGED:
0: Undefined, 1: Acknowledged, 2: Unacknowledged
Read only
ALARM_STATE
0:Undefined 0
1:Clear- Reported
2:Clear- Not reported
3:Active- Reported
4:Active- Not reported
Read only
TIME_STAMP Read only
SUBCODE value should match alert as stated under
FAILED_ENABLE
Read only
VALUE Read only
47 MAINT_PRI See index 42 FAILED_PRI 0 to 15 2 Read / Write
48 MAINT_ENABLE see alert table N/A
49 MAINT_MASK see alert table
50 MAINT_ACTIVE see alert table Read only
51 MAINT_ALM See index 46 FAILED_ALM
52 ADVISE_PRI See index 42 FAILED_PRI 0 to 15 2 Read / Write
53 ADVISE_ENABLE see alert table N/A Read / write
54 ADVISE_MASK see alert table Read / write
55 ADVISE_ACTIVE see alert table Read only
56 ADVISE_ALM See index 46 FAILED_ALM
31 INSTRUMENT_TEMP Indicates the internal temperature of the instrument N/A N/A Read only
STATUS
VALUE Indicates the internal temperature of the device in
degrees Celcius
57 HEALTH_INDEX Parameter representing the overall health of the device.
100 being perfect and 1 being non-functioning.
10 to 100 100 Read only
no alerts -> 100
ADVISE_ACTIVE -> -10 per advice
MAINT_ACTIVE -> - 40 per advise
FAIL_ACTIVE -> = 10 (10 also lowest value)
30 FLASH_LED For identification blink status led (5 min.)
0: finished
1:start
0 to 1 N/A Read / Write
58 FF_COMM_STAT Indicates quality of FF communications
FF_COMM_ATTEMPTS - States the number of attempts.
When at max, reset to 0 for timed out messages also!
0 to 65535 0 Read only
FF_COMM_TIME_OUT - States how manny of the
attempts were timed out
0 to 65535 0 Read only
59 PWA_SIMULATE Password protected and off when powercycled! If this is
set to 2 then all the alert parameters are writable 1:
sumulate off, 2 simulate enabled
1 and 2 1 Read / Write
Table 4.2 FieldQ™ Transducer Block (continued)
Alerts
Others