![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/1/65/1650e539-69f0-4245-a912-bf83b6459efa/1650e539-69f0-4245-a912-bf83b6459efa-bg14.png)
TM
Page 20
Reference manual Foundation Fieldbus Control module
DOC.RM.QC34.E Rev: A
October, 2006
Index
No.
Name Description Valid Range Initial Value Permission
36 BLOCK_ALM The block alarm is used for all configurations, hardware
connection failures and system problems in the block. The
cause of the alert is entered in the sub-code.
UNACKNOWLEDGED: 0 undefined, 1 acknowledged, 2
unacknowledged
0 to 2 Read / Write
ALARM_STATE 0:Undefined 0 1:Clear- Reported 2:Clear- Not
reported 3:Active- Reported 4:Active- Not reported
0 to 4 Read only
TIME_STAMP time Read only
SUB_CODE = BLOCK_ERR Read only
VALUE- A value can be added by the customer for configuring
alarms
Read only
37 ALARM_SUM Status and states of the alarms associated with the block 0: Discrete alarm
set when write
lock is turned off 7:
Block alarm
CURRENT- current status
UNACKNOWLEDGED - states unacknowledged alarms
UNREPORTED - states unreported alarms
DISABLED - states disabled alarms
38 ACK_OPTION When enabled, the device automatically acknowledges alerts
sent to the host
1 to 2 1 Read / Write
1 : Auto Acknowledge Disabled
2 : Auto Acknowledge Enabled
39 WRITE_PRI Priority of the alarm generated by clearing the Write Lock 0 to 15 0 Read / Write
40 WRITE_ALM Generated if the writelock is cleared
UNACKNOWLEDGED: 0 undefined, 1 acknowledged, 2
unacknowledged
0 to 2 0 Read / Write
ALARM_STATE 0:Undefined 0 1:Clear- Reported 2:Clear- Not
reported 3:Active- Reported 4:Active- Not reported
0 to 4 0 Read only
TIME_STAMP time 0 Read only
SUB_CODE - indicates what alarm 0 Read only
VALUE- A value can be added by the customer for configuring
alarms
0 Read only
41 ITK_VER Indicates the major revision number of the interoperability test
case used in certifying this device as interoperable
set by FF 4 Read only
42 DISTRIBUTOR Private Label Distributor. Identifies the company that is
responsible for the distribution of this Field Device to
customers
0x564144 Read only
43 DEV_STRING Currently not used
44 FB_OPTIONS Currently not used
45 DIAG_OPTIONS Currently not used
46 MISC_OPTIONS Currently not used
47 SOFTWARE_REVISION Software revisions of FF card and controler card
RB_SFTWR_REV_MAJOR 0 to 255 N/A Read only
RB_SFTWR_REV_MINOR 0 to 255 N/A Read only
RB_SFTWR_REV_BUILD 0 to 255 N/A Read only
CTRL_CRD_SWARE_REV interpret MSB.LSB 0 to 255 N/A Read only
0 Read only
Table 4.1 FieldQ™ Resource Block (Continued)