Toshiba MMU-AP0071MH Cassette Player User Manual


 
61
Check code
Main
remote
controller
P17
P19
P20
Outdoor 7-segment display
Check code
P17
P19
P20
Auxiliary code
Detected outdoor unit No.
Detected
position
I/F
I/F
I/F
Check code name
Discharge temp
TD2 error
4-way valve
operation error
High-pressure
protective operation
Status
All stop
All stop
All stop
Error detection condition
Discharge temperature (TD2)
exceeded 115°C.
When abnormal refrigerating cycle
data was detected in heating
Pd sensor detected 3.6MPa or
more.
Check item (position)
Check full opening of outdoor service valves (gas side, liquid side).
Check clogging of outdoor PMV (PMV1, 2).
Check characteristics of TD2 sensor resistance value.
Check 4-way valve error.
Check leakage of SV42 circuit.
Check SV4 circuit. (Miscabling and misinstallation of SV41 and SV42)
Check leakage of SV5 valve circuit.
Check SV6 circuit. (Clogging, Valve operation error)
Check mispiping of discharge gas/suction gas main pipe.
Check Flow selector unit.
Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.)
Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit
and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.
Error of 4-way valve error.
Check coil error and connector connection of 4-way valve.
Check characteristics of TS1/TE1 sensor resistance value.
Check characteristics of Pd, Ps pressure sensor output voltage.
Check misconnection of TE1 and TL sensors.
Check Flow selector unit.
Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.)
Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas).
Check Pd pressure sensor error.
Check full opening of service valves (Gas side, Liquid side).
Check outdoor fan error.
Check outdoor fan motor error.
Check clogging of outdoor PMV. (PMV1,2)
Check clogging of indoor/outdoor heat exchangers.
Check air short-circuiting in outdoor unit.
Check clogging of SV2 circuit.
Check outdoor P.C. board (I/F) error.
Check indoor fan system error. (Cause of air volume decrease)
Check valve opening of indoor PMV.
Check miscabling of communication line between indoor and outdoor.
Check operation error of check valve of discharge pipe.
Check circuit of gas balance SV4 valve.
Check mispiping of discharge gas/suction gas main pipe.
Check operation error of check valve of discharge gas pipe.
Check circuit of SV11 valve. (Clogging, OFF at one side only)
Check clogging of circuit at auxiliary heat exchanger side. (Miswiring, Disconnection, Wiring missing)
Check Flow selector unit.
Check leakage of SVD valve and operation error.
Check wiring inside of FS unit. (SVD/SVS coil miswiring, etc.)
Check wiring between FS unit and indoor unit. (Miswiring, Disconnection, Wiring missing)
Check circuit of SV5 valve.
Check refrigerant overcharge.