Toshiba MMU-AP0071MH Cassette Player User Manual


 
40
Table: Function selecting item numbers (DN)
(Items necessary to perform the applied control at the local site are described.)
DN
01
02
03
04
06
0d
0E
0F
10
11
12
13
14
1E
28
2A
2E
31
32
33
5d
60
Item
Filter display delay timer
Dirty state of filter
Central control address
Specific indoor unit priority
Heating temp shift
Existence of [AUTO] mode
Follows operation mode of
the header unit
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Temp difference of [AUTO]
mode selection COOL
HEAT, HEAT COOL
Automatic restart of power
failure
Selection of option/error
input (CN70)
HA terminal (CN61) select
Ventilating fan control
TA sensor selection
Temperature unit select
High ceiling selection
(Air volume selection)
Timer set
(Wired remote controller)
Description
0000 : None 0001 : 150H
0002 : 2500H 0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit to 0064 : No.64 unit
0099 : Unfixed
0000 : No priority 0001 : Priority
0000 : No shift 0001 : +1°C
0002 : +2°C to 0010 : +10°C
(Up to +6 recommended)
0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)
0000 : Does not follow
0001 : Follows
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0014: Compact 4-way Air Discharge Cassette
0000 : Unfixed 0001 to 0034
0001 : No.1 unit to 0030 :No.30 unit
0001 : No.1 unit to 0064 :No.64 unit
0000 : Individual 0001 :Header unit of group
0002 : Follower unit of group
0000 : 0 deg to 0010 :10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None 0001 :Restart
0000 : Filter input 0001 :Alarm input (Air washer, etc.)
0002 : None
0000 : Usual 0001 :Leaving-ON prevention control
0002 : Fire alarm input
0000 : Unavailable 0001 :Available
0000 : Body TA sensor 0001 :Remote controller sensor
0000 : °C (at factory shipment)
0001 : °F
[Compact 4-way Air Discharge Cassette type]
0000 : AP007 to AP012; Below 2.7m
AP015; Below 2.9m
AP018; Below 3.2m
0002 : AP015; Below 3.2m
AP018; Below 3.4m
0003 : AP015, AP018; Below 3.5m
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
At shipment
0002 : 2500H
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2°C
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Not provided
0000 : Heat pump
0014:
Compact 4-way A/D only
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : None
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Body TA sensor
0000 : °C
0000 : Standard
0000 : Available