Please specify the following parameters when ordering a transmitter; process type, process
range (%, ppm), thermocouple type, temperature scale F/C, analog output 1 process and
scale, analog output 2 process and scale.
Typical Oxygen Transmitter Calibration
(F840030)
Calibration
Function
Measured Value or
Input
Output / Units
Cold Junction Room Temp °F
Thermocouple
min
800°F (B type)
standard t/c type
°F
Thermocouple
max
3000°F (B type)
standard t/c type
°F
Millivolt 0.0 mV Millivolts
Millivolt 2000 mV Millivolts
Analog 1 Zero 0% O2 4.0 mA +/- 0.1
Analog 1 Span 20.9% O2 20.0 mA +/- 0.1
Analog 2 Zero 800°F +/- 5° 4.0 mA +/- 0.1
Analog 2 Span 3000°F +/- 5° 20.0 mA +/- 0.1
Typical Carbon Transmitter Calibration
(F840031)
Calibration
Function
Measured Value or
Input
Output / Units
Cold Junction Room Temp °F
Thermocouple
Min
MUST BE
SPECIFIED
°F
Thermocouple
Max
MUST BE
SPECIFIED
°F
Millivolt 0.0 mV Millivolts
Millivolt 2000 mV Millivolts
Analog 1 Zero 0% Carbon 4.0 mA +/- 0.1
Analog 1 Span 2.55% Carbon 20.0 mA +/- 0.1
Analog 2 Zero MUST BE
SPECIFIED
4.0 mA +/- 0.1
Analog 2 Span MUST BE
SPECIFIED
20.0 mA +/- 0.1