Page 13 of 23
11/14/2006 Rev. 14
BLOCK 0
HEX DEC PARAMETER DESCRIPTION READ/WRITE
DEFAULT = 150
05 5 EVENT
LDLN
LOW BYTE – INPUT EVENT
CONFIGURATION
Bits 0 – 3
0000 = None
0001 = Auto Mode Selected
0010 = Remote Setpoint Selected
0011 = Acknowledge alarms
0100 = Timer Hold
0101 = Timer End
0110 = Timer Start
0111 = Start probe test
1000 = Process hold
Bits 4 – 7 not used.
UPPER BYTE – LOAD LINE
READ/WRITE
06 6 CJTRM
HADR
LOW BYTE – COLD JUNCTION TRIM
COLD JUNCTION TRIM (unsigned integer)
RANGE = –128 TO +127 WHERE
1 COUNT = 1 DEG (C or F) and –128 = 65408
HIGH BYTE – HOST ADDRESS
BITS 0-7
RANGE = 0 – 255
07 7 SPARE SPARE
08 8 CONFIG0 Input Configuration
BITS 0-3 TC Input TYPE
0000 = B (DEFAULT)
0001 = E
0010 = J
0011 = K
0100 = N
0101 = R
0110 = S
0111 = T
1000 = SPARE
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = SPARE
1101 = SPARE
1110 = SPARE
1111 = SPARE
BIT 4 = SPARE
BIT 5 0 = NO CJ APPLIED, 1 = CJ APPLIED
BIT 6 0 = °F, 1 = °C
BIT 7 0 = 60HZ FILTER
BIT 8 – 11 Millivolt Input TYPE
0000 = LINEAR (DEFAULT)
All other bit combinations are spare
BITS 12 – 15 are spare
READ/WRITE
09 9 CONFIG2 SETUP VALUES