Specifications
Operating Conditions – All Models
Parameter
Reference
Condition
(at zero
static)
Rated Condition Operative Limits
Transportation
and Storage
°C °F °C °F °C °F °C °F
Ambient Temperature
25 ±1 77 ±2 -25 to 70 -13 to 158 -40 to 85 -40 to 185 -55 to 125 -67 to 257
Process Interface
Temperature
25 ±1 77 ±2 See Figure 13 -55 to 125 -67 to 257
Humidity %RH
10 to 55 0 to 100 0 to 100 0 to 100
Maximum Allowable
Working Pressure (MAWP)
MAWP is minimum of Body Rating or Seal Rating (See Model Selection Guide for Seal
MAWP)
Body MAWP
STR93D 750 psig (52 bar)
STR94G 500 psig (35 bar)
Vacuum Region, Minimum
Pressure - mmHg absolute
inH
2
O absolute
atmospheric
atmospheric
See Figure 13
Supply Voltage, Current,
and Load Resistance
Voltage Range: 10.8 to 42.4 Vdc at terminals
Current Range: 3.0 to 21.8 mA
Load Resistance: 0 to 1440 ohms (as shown in Figure 14)