Reference Manual MAS2600: Description and Technical Data
Ed 21 December 2014
6
Technical Specification
Transducer Ranges
Gauge 0 - 3.5 / 0 - 7 / 0 - 16 / 0 - 35 m H
2
O
Absolute 0 - 20.394 / 0 - 35.690 m H
2
O
Accuracy
± 0.25% F.S. at 20°C
Stability
Max. ± 0.1% / Year
TEB (Total Error Band)
± 0.4% F.S. at ±0 to +50°C
± 2.0% F.S. at -20 to +80°C
Overload Capability
Minimum 4 x transducer range with no changes in calibration.
6 x transducer range burst pressure.
Built-in Temperature Sensor Pt100
Optional (for safe area only)
Output Current
4-20 mA DC, loop powered 2-wire system
Current Limiting
Typical: 25 mA
Maximum: 32 mA
Sensor Materials
Housing Titanium Grade 2
Diaphragm Titanium Grade 4
Transducer cable
Safe area Maximum 300 m
Intrinsically safe in
hazardous area
Standard cable: 44m
High temperature cable: 34 m
Operating Temperature Ranges
Safe Area Transducer -20° to +125°C
Standard cable -20° to + 80°C
High temperature
cable
-20° to +125°C
Amplifier -20° to + 80°C
Intrinsically safe in
Hazardous Area
Transducer -20° to +80°C
Standard cable -20° to + 80°C
High temperature
cable
-20° to + 80°C
Amplifier -20° to + 80°C
Ingress Protection
Transducer IP 68
Amplifier IP 56
Intrinsic Safety (IS)
Ex ia IIC T4 compliant.