Forepeak Tank
If transducer measuring range > tank height: Select the next measuring range.
Example:
Tank height 12 m.
Based on the tank height a transducer with a measuring range of 16 mH
2
O should be selected.
However, due to the dynamic conditions in the forepeak tank, a transducer with a measuring range
of 35 mH
2
O, i.e. the next in line, should be selected.
Turn amplifier range select switch to range No. 6.
Draft
Transducer measuring range > max. draft minus sensor position.
This rule applies provided the transducer is mounted in accordance with the installation drawing for
draft transmitters (vent pipe min. 1"). The sensor may be mounted directly on the sea valve with an
air release valve depending on ship type and environment, always consult Marine Tank Management
for proper installation guidance.
TWO WIRE TRANSMITTER
2600 SERIES
90-C.95948
T5
Cint = 10 nF
C
CERTIFICATE REF.:
4-20 mA
Lint = 20 uH
x
i
EE
X
a
MARINE AUTOMATION DENMARK
S/N:
Umax = 33 V
T amb.: -40 to +85 °C
I 45 mA
K =
<
2600
MAS2600 amplifier box
Vent pipe min. 1”
Weather deck
Min. Draft
Class approved
sea valve
Sensor pos. above
ships hull
Ships hull