Start-Up Procedure: Apply power to the system
InfraStruXure System - Installation and Start-Up 33
3. Command the UPS to turn off power to the
load:
a. Press the
ESC key at the top-level status
screen to open the top-level menu and have
access to eight submenus.
b. Select Control, and press the
ENTER key.
Top-Level Menu
c. Select Turn Load Off from the Control
menu, and press the
ENTER key.
Control Menu
d. On the next screen: select Yes, UPS Load
OFF, and press the
ENTER key.
Confirmation Screen
The LOAD ON LED turns off and the
interface displays the following two screens:
4. Set the UPS System Enable switch to OFF,
and then set the UPS DC Disconnect circuit
breaker and to OFF.
5. If applicable, set the XR Battery Enclosure
DC Disconnect circuit breaker to OFF.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load Off
Confirm
Yes, UPS Load OFF
No, Abort
UPS has been
commanded to turn
load power off...
UPS load is off
Press any key...
px0003a