Start-Up Procedure: Apply power to the system
InfraStruXure System - Installation and Start-Up 31
8. Secure the power module:
a. Tighten the screws on each side of
the power module.
b. Turn the locking latch clockwise
until the arrow on the knob faces the
power module.
Note: The power module will not start unless the locking latch is engaged.
9. Set the UPS DC Disconnect circuit breaker to ON, and then set the
UPS System Enable switch to ON.
10. If applicable, set the XR Battery Enclosure DC Disconnect
circuit breaker to ON.
When the System Enable switch is in the ON position, the UPS
is running on battery. The Startup screen appears on the display
interface of the Symmetra PX UPS.
Then, the top-level status screen appears on the display interface.
This may take up to 40 seconds.
px0019a
px0013a
PowerView RM
Rev: 000 English
Please wait...
Fuel %
Load %
Runtime:
||||||||||||
|||
1hr 2m
In 000V out000V 60Hz