38 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variable and Configuration Property Definitions
This network variable provides the pressure of the refrigerant in the evaporator on
circuit 4. This refrigerant pressure is sometimes referred to as the evaporator suction
pressure.
Default: NaN
Invalid value: NaN
nvoEvapRfgtTmpC1
Evaporator refrigerant temperature—circuit 1, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the evaporator on
circuit 1. This refrigerant temperature is sometimes referred to as the evaporator suction
temperature.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEvapRfgtTmpC2
Evaporator refrigerant temperature—circuit 2, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the evaporator on
circuit 2. This refrigerant temperature is sometimes referred to as the evaporator suction
temperature.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEvapRfgtTmpC3
Evaporator refrigerant temperature—circuit 3, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the evaporator on
circuit 3. This refrigerant temperature is sometimes referred to as the evaporator suction
temperature.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEvapRfgtTmpC4
Evaporator refrigerant temperature—circuit 4, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the evaporator on
circuit 4. This refrigerant temperature is sometimes referred to as the evaporator suction
temperature.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEvapWFlowRate
Evaporator water flow rate, SNVT_flow