ACC-SVN100A-EN • LonTalk Communication Interface 37
Network Variable and Configuration Property Definitions
nvoEntChWTemp
Evaporator entering water temperature, SNVT_temp_p
This network variable provides the temperature of the water entering the evaporator.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEntCndWTemp
Condenser entering water temperature, SNVT_temp_p
This network variable provides the temperature of the water entering the condenser.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoEvapRfgtPrsC1
Evaporator refrigerant pressure—circuit 1, SNVT_press_f
This network variable provides the pressure of the refrigerant in the evaporator on
circuit 1. This refrigerant pressure is sometimes referred to as the evaporator suction
pressure.
Default: NaN
Invalid value: NaN
nvoEvapRfgtPrsC2
Evaporator refrigerant pressure—circuit 2, SNVT_press_f
This network variable provides the pressure of the refrigerant in the evaporator on
circuit 2. This refrigerant pressure is sometimes referred to as the evaporator suction
pressure.
Default: NaN
Invalid value: NaN
nvoEvapRfgtPrsC3
Evaporator refrigerant pressure—circuit 3, SNVT_press_f
This network variable provides the pressure of the refrigerant in the evaporator on
circuit 3. This refrigerant pressure is sometimes referred to as the evaporator suction
pressure.
Default: NaN
Invalid value: NaN
nvoEvapRfgtPrsC4
Evaporator refrigerant pressure—circuit 4, SNVT_press_f