Emerson 3108 Satellite Radio User Manual


 
Quick Start Guide
11
December 2014
Configuration
The transmitter can be configured and verified using a Field Communicator or a
Rosemount 3490 Series Control Unit.
The parameters in this section are for a sufficient for a basic level, contents (volume),
or open channel flow application. For a more advanced application, refer to the
Rosemount 3107 and 3108 Product Manual (00809-0200-4840).
Transmitter base units
When the transmitter is shipped from the factory, the default factory setting for Base
Units is “metric” or “imperial ft” depending on the model order code.
Note
Keep a record of your programmed settings. Changing the base units will reset
parameters to their default factory settings in the appropriate units.
Field Communicator and AMS
To view or change the transmitter base units:
1. From the Home screen,
select
3: Service Tools.
2. Select
4: Maintenance.
3. Select
3: Utilities.
4. Select
3: Set Base Units.
5. Select new base units.
Note
When on-screen messages appear, take action if needed and press “OK”.
Rosemount 3490 Series Control Unit
To view or change the transmitter base units:
1. From the Main Menu screen, select
SETUP.
2. Select the transmitter (e.g. “
Tx1: 3107”).
3. Select
SYSTEM, and then select Base Units.
4. Select new base units.
Note
To get the same base units on the control unit, switch the power off and then on
again. The control unit prompts for the transmitter’s
Bottom Reference value in
the new base units.
Set Base Units (ft)
m
ft
in
ft
ENTER
ABORT
(Field Communicator screen)
Base Units
Esc=Quit =Edit
metric
(Rosemount 3491 screen)