EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
19 74-2958—1
Outdoor Air Humidity (W7750B,C
only):
T
pe: Volta
e/Current.
Supported Sensors: C7600B1000 and C7600B1018
2 to 10V
, C7600C1008
4 to 20mA
.
Return Air Humidity (W7750B,C
only):
T
pe: Volta
e/Current.
Supported Sensors: C7600B1000 and C7600B1018
2 to 10V
, C7600C1008
4 to 20mA
.
Outdoor Air Enthalpy (W7750B,C
only):
T
pe: Current.
Supported Sensors: C7400A1004
4 to 20mA
.
Return Air Enthalpy (W7750B,C
only):
T
pe: Current.
Supported Sensors: C7400A1004
4 to 20mA
.
Air Filter Differential Pressure (W7750B,C
only):
T
pe: Volta
e.
Supported Sensors: Third part
2 to 10V, 0 to 5 inw
1.25 kPa
differential pressure sensors.
CO
2
Sensor (W7750B,C
only):
T
pe: Volta
e.
Supported Sensors: Third part
0 to 10V, 0 to 2000 ppm
CO
2
sensors.
Monitor Sensor for network use (W7750B,C
only):
T
pe: Volta
e.
Supported Sensors: Third part
2 to 10V, 2 to 10 volts
displa
ed.
DIGITAL INPUTS:
NOTE: Onl
one of each t
pe of input is allowed. For
example, onl
one Smoke Monitor is allowed. No
duplicate Smoke Monitors are usable on the same
controller.
Dr
-contact inputs are sensed usin
a 9 milliamp at 4.8 volts
detection circuit. It is ver
important that the device used
contains hi
h
ualit
, noncorrodin
contacts with resistivit
that does not de
rade; that is, increase over time. Use noble
metal
such as
old or silver
, or pimpled or sealed contacts to
assure consistent, lon
-term operation.
Two of the followin
Di
ital Inputs
DIs
can be confi
ured
when usin
the W7750A, and four of the followin
when usin
the W7750B,C:
— Fan Status:
Contact Closed = Fan on
— IAQ Switch:
Contact Closed = Poor Air Qualit
— Time Clock:
Contact Closed = Occupied Mode; Contact Open =
Unoccupied Mode
— Schedule Master:
Contact Closed = Local time clock is used as master time
clock
— Economizer Enable Si
nal:
Contact Closed = Economizer Enabled for coolin
use
— Smoke Monitor:
Contact Closed = Smoke Detected
— Dirt
Filter:
Contact Closed = Dirt
Filter
— Shutdown Si
nal:
Contact Closed = Shut off all e
uipment
— Occupanc
Switch:
Contact Closed = Room is Occupied; Contact Open =
Room is Unoccupied
— Window Monitor:
Contact Closed = Window is Closed
— Coil Freeze Stat:
Onl
use this DI when usin
E-Vision.
Contact Closed = Coil Freeze condition sensed
— Wall Module B
pass Pushbutton:
Momentar
DI
See Appendix B—Se
uences of Operation
for b
pass details.
TRIAC OUTPUTS ON THE (W7750B,C MODELS ONLY):
— Power ratin
s: 20 Vac to 30 Vac at 25 mA MIN to 500 mA
MAX current for an
volta
e.
When an
device is ener
ized b
a Triac, the device
must be able to sink a minimum of 25 mA.
NOTE: Triacs sink current to the 24 Vac common
COM
terminal on the W7750B,C Models
; see Fi
. 30 for
wirin
example.
IMPORTANT
If non-Honeywell motors, actuators, or transducers
are to be used with Excel 10 Controllers, Triac com-
patibility must be verified (see previous NOTE).
DIGITAL OUTPUTS:
COOL STAGE 1
COOL STAGE 2
COOL STAGE 3
COOL STAGE 4
HEAT STAGE 1
HEAT STAGE 2
HEAT STAGE 3
HEAT STAGE 4
CHANGE OVER RELAY
FAN
AUX ECON
OCCUPANCY STATUS
ECON OPEN
ECON CLOSE
COOL OPEN
COOL CLOSE
HEAT OPEN
HEAT CLOSE
HEAT COOL STAGE 1
HEAT COOL STAGE 2
HEAT COOL STAGE 3
HEAT COOL STAGE 4
FREE1
NOTE:
Free1
,
Free1 Pulse On
and
Free1 Pulse Off
are three separate and uni
ue di
ital output points. Because
the
are not related, the
all can be confi
ured in a CVAHU
controller at the same time.
FREE2
FREE1 PULSE ON
FREE1 PULSE OFF
ECON PWM
HEAT PWM
COOL PWM
UNUSED