INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installationand Operation Manual S 164201691 Rev 1 www.powerware.com
A-13
Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)
Basic Unit Rating
Units Rating 50/60 Hz
PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load
PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load
kVA/kW
500/400 500/450 625/500 625/562
Input and Output Voltage Volts 400 400 400 400
AC Input to UPS Rectifier (0.95 Min. pF)
(3) Phases, (1) Neutral, (1) Ground
Amps* 880 910 1100 1138
Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current
A
AWG or kcmil
(each)
350
(4)
400
(4)
600
(4)
700
(4)
AC Input to MBC (UPS Bypass)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
DC Input from Battery to UPS
(1) Positive, (1) Negative
Vdc
Amps @ (2.0V/cell)
480
877
480
987
480
1097
480
1234
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
400
(3)
400
(3)
400
(4)
500
(4)
AC Output to Optional SBM
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
E
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
NOTE Callout letters A, B, C, D, and E map to Figure A-8.