INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installationand Operation Manual S 164201691 Rev 1 www.powerware.com
A-13
Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)
Basic Unit Rating
P
W
9
3
1
5
6
2
5
/
4
0
0
d
P
W
9
3
1
5
6
2
5
/
5
0
0
0
8
L
i
F
L
d
Units Rating 50/60 Hz
PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load
PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load
kVA/kW
500/400 500/450 625/500 625/562
Input and Output Voltage Volts 400 400 400 400
AC Input to UPS Rectifier (0.95 Min. pF)
(3) Phases, (1) Neutral, (1) Ground
Amps* 880 910 1100 1138
Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current
A
AWG or kcmil
(each)
350
(4)
400
(4)
600
(4)
700
(4)
AC Input to MBC (UPS Bypass)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
B
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
DC Input from Battery to UPS
(1) Positive, (1) Negative
C
Vdc
Amps @ (2.0V/cell)
480
877
480
987
480
1097
480
1234
Minimum Conductor Size
Number per Pole
C
AWG or kcmil
(each)
400
(3)
400
(3)
400
(4)
500
(4)
AC Output to Optional SBM
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
E
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
E
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
D
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
NOTE Callout letters A, B, C, D, and E map to Figure A-8.