GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split -- system air conditioner
unit suitable for ground or rooftop installation. Unit consists
of a hermetic compressor, an air--cooled coil, propeller-- type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil
or coil unit.
Quality Assurance
Unit will be rated in accordance with the latest edition of
ARI Standard 210.
Unit will be certified for capacity and efficiency, and listed
in the latest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards
and will carry the UL label of approval. Unit will have
c--UL approval.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500-- hr salt
spray test.
Air-- cooled condenser coils will be leak tested and pressure
tested.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled air conditioner
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puronr (R--410A), and special features required prior to
field start--up.
Unit
Cabinet
Unit cabinet, including louvered coil guard, will be
constructed of galvanized steel, bonderized, and coated
with a powder coat paint.
Fans
Condenser fan will be direct--drive foward--swept
propeller type, discharging air upward.
AIR--COOLED, SPLIT --SYSTEM AIR CONDITIONER
165A
1 --1/2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed, 1-- phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with coated steel
wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber split--post vibration
isolators.
Compressor will be covered with a sound absorbing
blanket.
Condenser
Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration
Components
Refrigeration circuit components will include liquid--line
back--seating shutoff valve with sweat connections,
vapor--line back-- seating shutoff valve with sweat
connections, system charge of Puronr (R-- 410A)
refrigerant, and compressor oil.
Unit will be equipped with high -- pressure switch, low
pressure switch and filter drier for Puron refrigerant.
Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at
a suction temperature of ______F/_C. The power
consumption at full load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil unit
will have a total net cooling capacity of _____ Btuh or
greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F/_C wet bulb and
_____ _F/_C dry bulb, and air entering the unit at _____
_F/_C.
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of satisfactory
operation within voltage limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.