York F*FV Stereo System User Manual


 
295421-YTG-B-0707
Unitary Products Group 7
Physical and Electrical Data
MODEL F4FP024H06T2* F4FP030H06T2* F4FP036H06T2* F4FP040H06T2*
Blower - Diameter Width 10x6 10x8 10x8 10x8
Motor
HP 1/4 1/3 1/2 1/3
Nominal RPM 1075 1075 1075 1075
Voltage 208/230
AMPS
Full Load 1.6/1.4 2.5/2.2 3.3/2.9 2.5/2.2
Locked Rotor 3.3/2.9 6.2/5.5 7.4/6.5 6.2/5.5
Filter
1
1. Field Supplied.
Type Disposable/Permanent
Size 16x20x1 16x20x1 20x20x1 20x20x1
Permanent Type Kit
1PF0601BK 1PF0601BK 1PF0602BK 1PF0601BK
Shipping/Operating Weight (lbs.) 98/93 105/100 115/109 121/115
MODEL F4FP042H06T2* F4FP045H06T2* F5FP048H06T2* F5FP060H06T2* F4FV060H06T2*
Blower - Diameter x Width 10x8 10x10 11x10 11x10 11x10
Motor
HP 3/4 1/3 1.0 1.0 1.0
Nominal RPM 1130 925 1050 1050 1200
Voltage 208/230 230
Amps
Full Load 4.4/3.8 3.0/2.7 7.6 7.6 7.8/7.0
Locked Rotor 11.9/10.3 4.8/4.1
Filter
1
Type Disposable/Permanent
Size 20x20x1 22x20x1 22x20x1 22x20x1 22x20x1
Permanent Type Kit
1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping/Operating Weight (lbs.) 121/115 150/144 153/147 160/154 160/154
ELECTRICAL DATA - Cooling Only
Models
Total Motor Amps
Minimum Circuit
ampacity
Max. O.C.P.
1
Amps/
Type
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay Fuse.
Minimum Wire
Size A.W.G.
208V 240V 208V 240V
F4FP024H06T2* 1.6 1.5 2.0 1.8 15 14
F4FP030H06T2* 2.5 2.3 3.2 2.8 15 14
F4FP036H06T2* 3.3 3.0 4.2 3.7 15 14
F4FP040H06T2* 2.5 2.3 3.2 2.8 15 14
F4FP042H06T2* 4.4 4.0 5.5 4.8 15 14
F4FP045H06T2* 3.1 2.6 3.9 3.4 15 14
F5FP048H06T2* 7.6 7.6 9.5 9.5 15 14
F5FP060H06T2* 7.6 7.6 9.5 9.5 15 14
VARIABLE SPEED MODEL
F4FV060H06T2* 15 14