Unitary Products Group 11
FIELD WIRING CONNECTION - COOLING ONLY FIELD WIRING CONNECTION - WITH HEATER KIT
ELECTRICAL DATA - 3 - (SINGLE SOURCE POWERSUPPLY) - COPPER WIRE
Models Heater Models
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
75°C Wire Size - AWG
208V 240V 208V 240V 208V 240V
F4FP024H06T2* 2HK06501025B 41.2 46.5 45 50 8 8
F4FP030H06T2*
2HK06501025B 42.2 47.4 45 50 8 8
2HK06501525B 42.2 47.4 45 50 8 8
F4FP036H06T2*
2HK06501025B 43.1 48.2 45 50 8 8
2HK06501525B 43.1 48.2 45 50 8 8
F4FP040H06T2*
2HK06501025B 42.2 47.4 45 50 8 8
2HK06501525B 42.2 47.4 45 50 8 8
F4FP042H06T2*
2HK06501025B 44.2 49.1 45 50 8 8
2HK06501525B 44.2 49.1 45 50 8 8
F4FP045H06T2*
2HK06501025B 42.8 47.9 45 50 8 8
2HK06501525B 42.8 47.9 45 50 8 8
F5FP048H06T2*
2HK06501025B 48.3 53.9 50 60 8 6
2HK06501525B 48.3 53.9 50 60 8 6
F5FP060H06T2*
2HK06501025B 48.3 53.9 50 60 8 6
2HK06501525B 48.3 53.9 50 60 8 6
F4FV060H06T2*
2HK06501025B 48.6 52.9 50 60 8 6
2HK06501525B 48.6 52.9 50 60 8 6