16 en | Installation MIYN46 Wall Transmitter
970.035b | F.01U.278.521 | v2.0 | 2012.12 User Manual US Bosch Security Systems
4.7 General configuration
The * marks a factory setting.
(o)
MIYN46 Wall Transmitters that feature the output relays are delivered with the Staff Pres-
ence Processing activated (B6 open). Models that do not feature the output relays are deliv-
ered with the Staff Presence Processing disabled (B6 soldered).
Bridge State Function
B3 Open* Technical Alarms are not repeated.
B4 Soldered* Calls are not repeated.
B5 Open* A daily message is sent every 24 hours.
Soldered Daily messages are suppressed.
B6
Open
(o)
Staff Presence Processing is activated.
Soldered
(o)
Staff Presence Processing is disabled.
B7 Open* Activation of J6 [4-5] terminal input causes a Reserve Call.
Soldered Activation of J6 [4-5] terminal input causes a Call for Assistance.
B8 Open* The Assistance Call does not depend on the presence of the Care Per-
sonnel.
Soldered The Assistance Call is possible only if the Care Personnel has signaled
his/her presence.