Alarms Audible alarm indicates power failure conditions, silenceable via alarm cancel switch. Once cancelled, alarm will resume
when approximately 2 min. of battery operation remain (assuming full load)
Switches 2 front panel-mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge
suppression
SURGE VOLTAGE WITHSTAND CAPABILITY: ANSI/IEEE C62.41 Catagories A & B 6KV/200/500 amp 100Khz
Ringwave and category B BiWave. SURGE VOLTAGE ATTENUATION: N-G 2000:1, L-G 240:1, L-N 100:1.
INSERTION LOSS: 65 db N-G from 10Khz to 100Khz, 45 to 60 db L-G from
AC suppression
response time
Instantaneous
Dataline
suppression
-
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
40
Shipping weight (kg) 18.2
Shipping
Dimensions
(HWD/in)
18.25 x 13.75 x 12
Shipping
Dimensions
(HWD/cm)
46.4 x 34.9 x 30.5
Unit weight (lbs) 36.4
Unit weight (kg) 16.5
Unit Dimensions
(HWD/in)
12.75 x 9.25 x 7.5
Unit Dimensions
(HWD/cm)
32.4 x 23.5 x 19.1
Material of
construction
PVC
Form factors
supported
Tower
Cooling method Fan
Battery Access Battery access door
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
COMMUNICATIONS
Network monitoring
port
USB
Software and
cabling included
USB cable included; PowerAlert software is available via free download from www.tripplite.com
WatchDog
compatibility
Yes with optional WATCHDOGSW
LINE / BATTERY TRANSFER
Transfer time from
line power to
battery mode
2-4 milliseconds