Series
Fan-Powered
CONFIDENTIAL DOCUMENT. FOR INTERAL USE ONLY. 56VAV-SLM005-EN
Performance
Data—Hot Water
Coil (I-P)
Trane—Fan Sizes 06, 07 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 1200 1400 1600 1800 2000 2200 2400 2600 2800 2900
1-Row 2 1.39 42.03 44.22 46.05 47.62 48.98 50.18 51.24 52.2 53.07 53.48
Capacity 3 2.86 46.71 49.39 51.83 53.94 55.8 57.46 58.94 60.29 61.52 62.09
MBH 4 4.8 49.64 52.68 55.33 57.66 59.83 61.79 63.56 65.17 66.65 67.35
5 7.18 51.57 54.87 57.76 60.32 62.62 64.69 66.63 68.44 70.1 70.88
6 10 52.93 56.43 59.5 62.23 64.68 66.91 68.95 70.82 72.57 73.42
7 13.23 53.95 57.6 60.81 63.67 66.24 68.59 70.73 72.71 74.55 75.42
2-Row 3 5.34 68.74 73.32 77.17 80.48 83.39 86 88.38 – – –
Capacity 4 8.88 73.59 79.09 83.78 87.87 91.52 94.83 97.88 100.7 – –
MBH 5 13.21 76.71 82.84 88.12 92.77 96.96 100.8 104.3 107.7 – –
6 18.3 78.86 85.45 91.18 96.25 100.9 105.1 109 112.7 – –
7 24.12 80.45 87.39 93.44 98.85 103.8 108.3 112.5 116.5 – –
Trane—Fan Sizes 03, 04, 05 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 600 800 1000 1200 1400 1600 1800 1900
1-Row 1 0.37 22.25 24.3 25.76 26.87 27.76 28.49 29.1 29.37
Capacity 2 1.25 27.22 30.38 32.88 34.94 36.64 38.08 39.31 39.87
MBH 3 2.6 29.44 33.22 36.19 38.62 40.7 42.55 44.16 44.89
4 4.37 30.69 34.83 38.13 40.87 43.2 45.22 47.01 47.84
5 6.57 31.49 35.88 39.4 42.34 44.86 47.05 49 49.89
6 9.17 32.05 36.62 40.3 43.39 46.04 48.36 50.42 51.37
7 12.17 32.46 37.16 40.97 44.17 46.92 49.34 51.49 52.48
2-Row 2 2.25 41.16 47.73 52.42 55.99 58.85 – – –
Capacity 3 4.61 44.52 52.72 58.88 63.74 67.77 71.22 74.26 –
MBH 4 7.68 46.3 55.45 62.5 68.2 72.99 77.16 80.88 –
5 11.45 47.4 57.16 64.81 71.07 76.4 81.07 85.28 –
6 15.87 48.14 58.33 66.41 73.08 78.8 83.85 88.42 –
7 20.95 48.68 59.19 67.58 74.56 80.58 85.92 90.77 –
Trane—Fan Sizes 01, 02 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 300 350 400 450 500 550 600 650 700
1-Row 0.5 0.16 10.06 10.53 10.92 11.24 11.52 11.77 11.99 12.18 12.35
Capacity 1 0.54 12.56 13.3 13.94 14.5 15.02 15.48 15.9 16.28 16.63
MBH 2 1.86 14.29 15.27 16.13 16.9 17.6 18.23 18.8 19.34 19.83
3 3.87 14.98 16.07 17.03 17.9 18.68 19.4 20.06 20.67 21.24
4 6.54 15.36 16.51 17.53 18.45 19.28 20.05 20.76 21.41 22.02
5 9.83 15.6 16.79 17.84 18.8 19.67 20.47 21.2 21.89 22.53
2-Row 1 1.02 19.08 20.66 21.96 23.07 24.02 24.85 25.59 26.25 –
Capacity 2 3.45 21.66 23.85 25.73 27.38 28.84 30.16 31.35 32.44 33.45
MBH 3 7.11 22.62 25.06 27.19 29.08 30.78 32.32 33.72 35.03 36.25
4 11.89 23.12 25.69 27.96 29.99 31.82 33.49 35.02 36.45 37.79
5 17.77 23.43 26.09 28.45 30.56 32.47 34.22 35.84 37.35 38.77