Operation
51RT-SVX20A-E4
To check the damper is functioning
correctly, the ECA is equipped with
an indicator light in the middle of
the board. This light operates as in
Table 42.
Table 47 - ECA board LED
While setting the minimum position
the damper may move towards the
new setting in several small steps.
Once the damper has remained in
the same position for 10 to 15
seconds it can be assumed it is in
the new position.
OFF: No Power or Failure
ON: Normal, OK to Economize
Slow Flash:
Normal, Not OK to
Economize
Fast Flash: Communications Failure
Pulse Flash: Error Code
1 Flash: Actuator Fault
2 Flashes: CO
2 Sensor
3 Flashes: RA Humidity Sensor
4 Flashes: RA Temp Sensor
5 Flashes: OA Quality Sensor
6 Flashes: OA Humidity Sensor
7 Flashes: OA Temp Sensor
8 Flashes: MA Temp Sensor
9 Flashes: RAM Fault
10 Flashes: ROM Fault
11 Flashes: EEPROM Fault
Figure 31 - Minimum fresh air adjustment
1 = ECA board
MIN POS.
OPEN=ON BOARD POT.