–23–
4-way Air Discharge Cassette Type
Installation Manual
Procedure 3
Using temp. setup / buttons, specify CODE
No. [ ].
Procedure 4
Using timer time / buttons, select SET DATA
[ ].
Procedure 5
Push button. When the display changes from
flashing to lit, the setup is completed.
To change settings of another indoor unit, repeat
from Procedure
2.
To change other settings of the selected indoor unit,
repeat from Procedure
3.
Use button to clear the settings.
To make settings after button was pushed, repeat
from Procedure
2.
Procedure 6
When settings have been completed, push button
to determine the settings.
When button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote control is accepted.)
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
(
1 2 3 4 5 6 ).
For the CODE No. in Procedure
3, specify [5d].
Select the setting data for Procedure
4 from the
“Height list of ceiling possible to be installed” table on
page 7 in this manual.
Using wireless remote control
Change the high-ceiling settings with the DIP switch on
the receiver section P.C. board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. board.
* However, once the setting is changed, setting to
0001 or 0003 is possible but setting to 0000 requires
a setting data change to 0000 using the wired remote
control (sold separately) with the normal switch
setting (factory default).
Restore the factory default
To return the DIP switch settings to the factory default,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote control, and then set the
data of CODE No. [5d] to “0000”.
Setup data SW501-1 SW501-2
0000
(Factory default)
OFF OFF
0001 ON OFF
0003 OFF ON
SW501-1
MCU(IC501)
SW501-2
23-EN