A SERVICE OF

logo

18
MOTOR DATA
Power Code Description — PSH Models
➂ ➃
Model
PSH130 PSH150 PSH170 PSH225 PSH280 PSH340
Power Electric
Code Power Horsepower
01
115/60/1 1/6 1/6 1/6 1/3 1/2 1/2
0
2
230/60/1 1/6 1/6 1/6 1/3 1/2 1/2
0
4
200/60/3 1/3 1/3 1/3 1/3 1/2 1/2
0
5
200/460/60/3 1/3 1/3 1/3 1/3 1/2 1/2
Power Code Description — BSH Models
➂ ➃ ➄
Power Model BSH130 BSH150 BSH170 BSH225 BSH280 BSH340
Code Electric Power HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
01
115/60/1 1/3 -13 3/4 -18 3/4 -18 3/4 -18 1 -16 1-1/2 -16
0
2
230/60/1 1/3 -13 3/4 -18 3/4 -18 3/4 -18 1 -16 1-1/2 -16
0
3
200-208/60/3 1/3 -13 3/4 -18 3/4 -18 3/4 -18 1 -16 1-1/2 -16
0
4
230/460/60/3 1/3 -13 3/4 -18 3/4 -18 3/4 -18 1 -16 1-1/2 -16
8
1
575/60/3 1/3 -14 3/4 -18 3/4 -18 3/4 -18 1 -16 1-1/2 -178
0
5
115/60/1 1/4 -21 1/2 -25 1/2 -25 3/4 -22 1 -18 1 -29
0
6
230/60/1 1/4 -21 1/2 -25 1/2 -25 3/4 -22 1 -18 1 -29
0
7
200-208/60/3 1/4 -21 1/2 -25 1/2 -25 3/4 -22 1 -18 1 -29
0
8
230/460/60/3 1/4 -21 1/2 -25 1/2 -25 3/4 -22 1 -18 1 -29
8
2
575/60/3 1/4 -165 1/2 -25 1/2 -25 3/4 -22 1 -18 1 -29
0
9
115/60/1 1/3 -15 1/2 -22 1/2 -22 1 -16 1-1/2 -23
1
0
230/60/1 1/3 -15 1/2 -22 1/2 -22 1 -16 1-1/2 -23
1
1
200-208/60/3 1/3 -15 1/2 -22 1/2 -22 1 -16 1-1/2 -23 2 -32
1
2
230/460/60/3 1/3 -15 1/2 -22 1/2 -22 1 -16 1-1/2 -23 2 -32
8
3
575/60/3 1/3 -166 1/2 -22 1/2 -22 1 -16 1-1/2 -177 2 -32
1
3
115/60/1 1/3 -57 3/4 -25
1
4
230/60/1 1/3 -57 3/4 -25
1
5
200-208/60/3 1/3 -57 3/4 -25
1
6
200/460/60/3 1/3 -57 3/4 -25
8
4
575/60/3 1/3 -167 3/4 -25
Motor Data and Total Unit Power Requirements — PSH Models
Voltage 115/60/1 230/60/1 200-208/60/3 230/460/3
Motor Motor Total Total Motor Motor Total Total Motor Motor Total Total Motor Motor Total Total
HP
Amps Rpm Amps Watts Amps Rpm Amps Watts Amps Rpm Amps Watts Amps Rpm Amps Watts
1/6
2.8 1075 4.6 400 1.5 1075 2.5 400
1
/3
5.4 1075 7.2 610 2.5 1075 3.5 610 1.9 1140 2.8 560 2.2/1.1 1140 3.2/1.6 560
1
/2
7.5 1075 9.3 800 3.5 1075 4.5 800 2.6 1140 3.5 850 3.0/1.5 1140 4.0/2.0 850
Unit Power Requirements - Blower BSH Models
115/60/1 230/60/1 200-208/60/3 230/460/60/3 575/60/3
Total Total Total Total Total Total Total Total Total Total
HP Amps Watts Amps Watts Amps Watts Amps Watts Amps Watts
1/4 7.2 520 3.7 520 2.5 500 2.4/1.2 500 0.9 500
1/3 6.4 515 3.3 515 2.7 530 2.6/1.3 530 1.1 530
1/2 10.3 730 4.8 730 3.4 730 3.6/1.8 730 1.3 730
3/4 12.8 1000 6.5 1000 4.1 970 3.8/1.9 970 1.5 970
1 15.2 1210 7.7 1210 4.9 1230 4.8/2.4 1230 1.9 1230
1-1/2 16.8 1690 8.5 1690 6.5 1630 6.2/3.1 1630 2.3 1630
2 - - - - 8.6 2080 7.6/3.8 2080 2.7 2080
Permanent split capacitor motors on models PSH130 through PSH340.
Split phase motors for 1/4 through 3/4 hp motors.Capacitor start motors are 1 through 2 hp.
Whenever 230V/1
φ
or 230V/3
φ
power is used, it is necessary to specify 230V/25V controls.Whenever 460V/3
φ
power is used, it is necessary to specify 230V/25V
controls and in addition, a 460V/230V 75VA step-down transformer (by others) is required. On 230V/3
φ
or 460V/3
φ
systems, the motor starter coil voltage (motor
starter by others) must be 230V. For 200V/3
φ
systems, the motor starter coil voltage (motor starter by others) must be 200V.
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor
manufacturer and Modine.All motors are totally enclosed. Single phase motors have built-in thermal overload protection.
575V motor available on blower units only.
Voltage