V5853; V5863
Three-way Cartridge Globe Valves
control hot and/or chilled water for
VAV terminal units, fan coil units,
small reheaters and recoolers in
electric/ electronic temperature
control systems. Used with the
M6410 3-position floating Non-
Spring Return Valve Actuator and
the M7410 selectable 0 to 10 Vdc
or 2 to 10 Vdc Non-Spring Return
Actuator. The 1/2 in. and 3/4 in.
valves are also compatible with the
M6435 floating Spring Return
Actuator, the M7435 selectable 0 to 10 Vdc or 2 to 10 Vdc
Spring Return Actuator, and the MP958 Pneumatic Actuator.
SPECIFICATIONS
Valve Type ............................................Cartridge Globe Valve
Body Pattern ........................................Three-way
Flow Characteristic ...............................A -port - Equal percentage for
1/2 and 3/4 in.
Linear for 1 to 1 1/2 in.
B-port - Linear @ 20% reduced
Cv
Connection Type ..................................Sweat , Female NPT
Controlled Medium ...............................Hot/Chilled Water with up to
50% Glycol
Leakage Rating ....................................less than 0.02% of
C
v
Maximum Safe Operating Pressure .....235 psi (1620 kPa)
Ambient Temperature Range ...............36 F to 230 F (2 C to 110 C)
Stem Travel ...........................................1/4 in. (6.4 mm)
Materials
(Body) ...................................................Brass
(Stem) ...................................................Stainless Steel
(Seat) ....................................................Brass
(Cartridge) ............................................Brass
(Plug/Ball/Disc) .....................................Brass
Includes ................................................Combination manual opener/
dust cap
FEATURES
• Long stroke allows wider range of control.
• Soft valve seat provides low leakage rate.
• Inserts for 1/2 in. and 3/4 in. valves are changeable without
draining valve when used with an insert replacement tool.
• Brass body and stainless steel stem.
• Threaded plastic cover/manual handle allows manual
operation.
• Easily installed in areas where space is limited.
DIMENSIONS DIAGRAM