“b” Function Defaults
Func.
Code
Name Description
Run
Mode
Edit
Initial data Units
B133
Decel. overvolt. suppress
proportional gain
Proportional gain when b130=01.
Range is: 0.00 to 5.00
0.20
B134
Decel. overvolt. suppress
integral time
Integration time when b130=01.
Range is: 0.00 to 150.0
1.0 sec
b145
GS input mode Two option codes:
00No trip (Hardware shutoff only)
01Trip
U
00 -
b150
Display ex.operator connected When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:
d001 ~ d030
U
001
b160
1st parameter of Dual Monitor Set any two "d" parameters in b160
and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range: d001 ~ d030
U
001
b161
2nd parameter of Dual Monitor
U
002
b163
Frequency set in monitoring Two option codes:
00Freq. set disabled
01Freq. set enabled
00 -
b164
Automatic return to the initial
display
10 min. after the last key operation,
display returns to the initial
parameter set by b038. Two option
codes:
00Disable
01Enable
00 -
b165
Ex. operator com. loss action Five option codes:
00Trip
01Trip after deceleration to a stop
02Ignore
03Coasting (FRS)
04Decelerates to a stop
02 -
b166
Data Read/Write select
00 Read/Write OK
01 Protected
U
00 -
b171
Inverter mode selection Three option codes:
00No function
01Std. IM (Induction Motor)
03PM (Permanent Magnet Motor)
U
00 -
b180
Initialization trigger
(*)
This is to perform initialization by
parameter input with b084, b085 and
b094. Two option codes:
00Initialization disable
01Perform initialization
U
00 -
b190
Password Settings A 0000(Invalid Password)
0001-FFFF(Password)
U
0000 -
b191
Password authentication A 0000-FFFF
U
0000 -
b192
Password Settings B 0000(Invalid Password)
0001-FFFF(Password)
U
0000 -
b193
Password authentication B 0000-FFFF
U
0000 -