SECTION 4 ADJUSTMENTS
4 --- 1
Time Delay Adjustment
Standard time de lays are set to customer specifications
(if none specified, standard factory settings are used).
To change a se tting, follow procedure on page 4-2. Use
Table 4-1 as a guide to time delay values and their corre-
sponding adjustment DIP switch or potentiometer.
Table4-1.TimeDelaySettings
DESCRIPTION LABELS
FACTORY
SETTING
ADJUSTMENT
RANGE
S3 DIP
SWITCH
ADJUSTMENT
POTENTIOMETER
Override Momentar
1second Actuator 1 on
1
Normal Source Outages
3secon
s
3seconds Actuator 1 off
1
TIMER 0 minutes 0to5
rans
er to
mergency
N/E
(full ccw)
minutes
2
Override Momentary
Emergency S. Outages
— 4seconds non-adjustable — — —
TIMER 30 minutes 1secondto
etrans
er to
orma
E/N
(full cw)
30 minutes
1
Unloaded Running
(Engine Cooldown)
— 5 minutes non-adjustable — — —
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points
are set to customer specifications (if none specified,
standard factory settings are used). To change a setting,
followprocedure onpage 4–2. Use Tables4-2 and 4–3fo r
settings and corresponding DIP switch actuators.
Any change in these settings may affect the
normal operation of the automatic transfer
switch.Thischangecould allowtheload circuits
to remain connected to a low voltage source.
Ta ble 4-2. Voltage and Frequency Settings. (
Shaded DIP switches are standard factory settings).
%ofnominal
S1 DIP
FACT . SET ADJ RANGE
SWITCH
95 % * Actuator 3 off
3
c
up 90 %
90 % Actuator 3 on
3
90 % *
Actuator 1 off
Actuator 2 off
21
Normal Source Voltage
85 %
Actuator 1 on
Actuator 2 off
21
DO
N Dropout
85 %
80 %
Actuator 1 off
Actuator 2 on
21
70 %
Actuator 1 on
Actuator 2 on
21
Emer
enc
Source
–– Pickup 90 % non-adjustable
Voltage
–– Dropout 75 % non-adjustable
––
–– Pickup 95 % non-adjustable
–– Dropout 85 % non-adjustable
––
Emergency Source
Frequency
60
50
60 Hz Actuator 4 off
4
Hz
60
50
z 60
z
50 Hz Actuator 4 on
4
3phase Actuator 6 off
6
o
tage
ases 3, 1 3
1 3
1phase Actuator 6 on
6
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
Table 4-3. Transformer Voltage A djust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
DESCRIPTION LABELS FACTORY SETTING ADJUSTMENT S3 DIP SWITCH
OW
LOW Actuator 2 off
2
o
tage
ust
4.2%
HI
HI Actuator 2 on
2