4
PERFORMANCE DATA
HVI Rated Energy Performance
MODEL MODE
SUPPLY
TEMP
NET
AIR FLOW
POWER
CONSUMED
(WATTS)
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVE-
NESS
LATENT
RECOVERY
MOISTURE
TRANSFER
TOTAL
RECOVERY
EFFICIENCY
_C _F L/S CFM
ERVBBLHA1150
Heat
0 32 30 64 66 61 75 0.62
0 32 46 97 77 60 71 0.58
0 32 66 141 137 57 69 0.52
--- 25 --- 13 22 47 92 49 80 0.56
Cool 35 95 31 65 63 56
ERVBBLHA1200
Heat
0 32 39 80 84 60 72 0.60
0 32 54 114 113 58 69 0.53
0 32 79 167 169 56 66 0.45
--- 25 --- 13 31 65 116 41 86 0.47
Cool 35 95 39 82 81 52
HRVBBLHA1150
Heat
0 32 31 66 85 69 81 0
0 32 56 119 124 60 70 0
0 32
--- 25 --- 13 34 72 114 62 80 0.08
Cool 35 95
HRVBBLHA1250
Heat
0 32 31 66 85 69 81 0
0 32 56 119 124 60 70 0
0 32 86 182 197 53 62 0
--- 25 --- 13 34 72 114 62 80 0.08
Cool 35 95
Ventilation Performance
MODEL
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
PA IN W.G. L/S CFM L/S CFM L/S CFM
ERVBBLHA1150
25 0.1 84 179 85 181 92 196
75 0.3 74 156 75 158 85 181
100 0.4 70 148 71 151 77 163
150 0.6 58 124 59 125 54 114
200 0.8 41 87 42 88 20 43
ERVBBLHA1200
25 0.1 105 222 106 225 106 225
75 0.3 93 198 94 200 100 212
100 0.4 86 183 88 186 93 198
150 0.6 70 148 71 150 75 158
200 0.8 50 107 51 108 29 61
HRVBBLHA1150
25 0.1 83 175 83 176 83 175
75 0.3 75 159 75 159 75 158
100 0.4 71 150 71 151 69 146
150 0.6 59 126 60 127 49 103
200 0.8 43 91 43 91 21 45
HRVBBLHA1250
25 0.1 110 234 112 237 112 237
75 0.3 98 208 100 211 99 210
100 0.4 89 189 91 192 91 193
150 0.6 71 151 72 153 70 149
175 0.7 64 136 65 138 44 94
NOTE: For additional data points, refer to HVI Directory at www.hvi.org
ERV / HRV