—2—
DIMENSIONS
A
SQ
AIR IN
AIR IN
3
/8-IN. DIA
TIEDOWN
KNOCKOUTS
(2) PLACES
H
G
F
E
L
K
J
AIR IN
M
N
AIR DISCHARGE
AIR IN
AIR DISCHARGE
NOTES:
1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE
SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F, MAX. 125°F.
3. SERIES DESIGNATION IS THE 14TH POSITION OF THE UNIT MODEL NUMBER.
4. CENTER OF GRAVITY .
AIR DISCHARGE
B
P
C
2
7
/8"
1
1
/4"
FIELD CONTROL SUPPLY
CONN
7
/
8
-IN. DIA
HOLE
FIELD POWER SUPPLY CONN
7
/
8
-IN. DIA HOLE WITH
1
1
/
8
-IN. DIA KNOCKOUT
AND 1
3
/
8
-IN. DIA
KNOCKOUT
3
/
8
-IN. DIA LIQUID
LINE CONN
D DIA VAPOR LINE CONN
A00015
DIMENSIONS (IN.)
UNIT
SIZE SERIES
UNIT DIMENSIONS MINIMUM
MOUNTING
PAD
DIMENSIONSABCDEFGHJKLMN P
024 A 22-1/2 31-15/16 3-3/16 5/8 3-11/16 18-1/8 19-3/4 22-1/4 14-3/8 19-9/16 22-1/16 10-1/4 9-1/2 11-5/8 22-1/2 x 22-1/2
030 A 22-1/2 29-15/16 3-3/16 3/4 3-11/16 18-1/8 19-3/4 22-1/4 14-3/8 19-9/16 22-1/16 10-1/4 9-1/2 11-1/2 22-1/2 x 22-1/2
036 A 22-1/2 33-15/16 3-3/16 3/4 3-11/16 18-1/8 19-3/4 22-1/4 14-3/8 19-9/16 22-1/16 10-1/4 9-1/2 15-1/2 22-1/2 x 22-1/2
042 A 30 27-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-3/4 20 27-1/16 29-9/16 15 13 14-1/2 30 x 30
048 A 30 27-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-3/4 20 27-1/16 29-9/16 15 13 14-1/2 30 x 30
060 A 30 39-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-3/4 20 27-1/16 29-9/16 15-1/2 14-3/4 14-1/2 30 x 30