ELECTRICAL
WARNING
Before servicing electrical components in the case or the doors or door frames make sure all power to case is
off. Always use a qualified technician.
NOTICE
For models with electronic ballast only:
For replacement ballast, use only ballast that complies with UL Type CC rating
if unit is equipped with electronic ballast.
Check voltage and amps drawn on (Page 12-15) to determine proper line and fuse or circuit breaker size. Check power
supply for low voltage. If voltage reads “230” with no load, and it drops below “207” when the compressor tries to start, it
is an indication of too small supply wiring or too long to run.
It is recommended that a separate circuit be run for each cabinet to prevent another appliance blowing the fuse or
breaker, causing loss of product.
IMPORTANT
This cabinet is pre-wired internally for separate 115 and 230-volt circuits. “Tapping” or feeding the 115-volt circuit from
230-volt supply may result in overloaded circuit breakers or blown fuses and damage to electrical system, thereby
voiding the warranty.
The cabinet should be grounded.
TEMPERATURE CONTROL
The BMG/TMG cabinet has a temperature control that is adjustable from #1
(warmest setting) to #7 (coldest setting). All the above controls are
accessible by opening the left-hand door.
LEG AND CONDENSATE PAN INSTALLATION FOR TOP MOUNT
CABINETS ONLY
1. Screw legs into existing crate mounting
holes.
2. Mount pan and bracket assembly to rear
of cabinet with 2 large sheet metal screws
(supplied). Be sure pan is located directly
under cabinet drain
Temperature
Control