White Rodgers 24A06G-1 Speaker User Manual


 
3
WIRING AND OPERATION (cont.)WIRING AND OPERATION (cont.)
WIRING AND OPERATION (cont.)WIRING AND OPERATION (cont.)
WIRING AND OPERATION (cont.)
All wiring should be done in accordance with local and national electrical codes and ordinances.
WIRING WIRING
WIRING WIRING
WIRING
Line Voltage Low Voltage
Line Voltage Field Low Voltage Field
OPERATIONOPERATION
OPERATIONOPERATION
OPERATION
HeatingHeating
HeatingHeating
Heating
As the “Heat” contacts of the thermostat close, bimetal heater
#1 is energized. Approximately 45 seconds later, the warping
action of bimetal heater #1 closes line voltage switch #1 to
energize the heating load. When the "Heat" contacts open,
heater #1 cools for approximately 45 seconds before switch #1
opens to de-energize the heating load.
CoolingCooling
CoolingCooling
Cooling
As the "Cool" contacts of the thermostat close, bimetal heater
#2 is energized. Approximately 45 seconds later, the warping
action of bimetal heater #2 closes line voltage switch #2 to
energize the cooling load. When the "Cool" contacts open,
heater #2 cools for approximately 45 seconds before switch #2
opens to de-energize the cooling load.
Fig. 3. Using Heating-Cooling Thermostat toFig. 3. Using Heating-Cooling Thermostat to
Fig. 3. Using Heating-Cooling Thermostat toFig. 3. Using Heating-Cooling Thermostat to
Fig. 3. Using Heating-Cooling Thermostat to
Operate Heating and Cooling LoadsOperate Heating and Cooling Loads
Operate Heating and Cooling LoadsOperate Heating and Cooling Loads
Operate Heating and Cooling Loads
YORW
TYPE 1F36 HEATING-COOLING THERMOSTAT
FIXED
COOLING
ANTICIPATOR
THERMOSTAT
SWITCH
BIMETAL
HEAT
ADJUSTABLE
HEATING
ANTICIPATOR
TYPE 24A06 DUAL LEVEL TEMP
WHITE
BLACK W/
WHITE STRIPE
RED
BIMETAL
HEATER #2
BIMETAL
HEATER #1
SWITCH #1
SWITCH #2
TRANSFORMER
HEATING
LOAD #1
RED
BLACK
BLUE
L1
L2
LINE
BLACK W/RED STRIPE
RED W/BLACK STRIPE
COOLING
LOAD
L1
L2
LINE
The Emerson logo is a
trademark and a service mark
of Emerson Electric Co.