119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
TANDBE RG
Telepresence T3
HVAC REQUIREMENTS
The following HVAC (heating, ventilation, air-conditioning) requirements apply to
the TANDBERG Telepresence T3:
• Power consumption System: 1725 W
• Power consumption Table: 300 W
• Power consumption Lighting: 1300 W
• Noise from air-conditioning should be less or equal to 27 dB(A) measured at
all seating positions.
Make sure that HVAC mounting neither conflicts with the ceiling lights positions
nor the document camera position.
A detailed drawing of the ceiling mounting of the lights can be found overleaf,
while the drawing 119082 on page 14 shows the position of the document camera.
Note: Dimensions are between floor and
underside of light modules.
Note: The HVAC equipment must not
be mounted in a way so that it prevents
correct mounting of the ceiling lights and the
document camera. Consult the TANDBERG
Telepresence T3 Room Installation Guide for
more on this.
228 cm
7’5
3
4
Centerline
Tip! An average person emits approximately
65 W at rest. You may want to consider this
when calculating the HVAC requirements.