6
6-10
EMC Fibre Channel Storage System Model FC4700 Configuration Planning Guide
Storage-System Hardware
Current draw At 100 v ac input – Deskside DPE/DAE: 12.0
A; Rackmount DPE: 8.0 A max SPS: 1.0 A
max per unit during charge
Power consumption Deskside DPE/DAE: 1200 VA
Rackmount DPE: 800 VA max SPS: 100 VA
per unit during charge
Power cables (single or dual)
ac inlet connector IEC 320-C14 power inlet
Deskside power cord USA 1.8 m (6.0 ft): NEMA
6-15P plug
Outside USA Specific to country
Operating environment
Temperature 10
o
C to 40
o
C (50
o
F to 104
o
F)
Relative humidity Non-condensing, 20% to 80%
Altitude 40
o
C to 2,438 m (8,000 ft); 37
o
C to 3,050 m (10,000 ft)
Heat dissipation (max) Deskside DPE/DAE: 4115x10
3
J/hr (3900 BTU/hr) max
estimated
Rackmount DPE: 2736x10
3
J/hr (2594 BTU/hr) max
estimated
Air flow Front to back
Service clearances
Front 30.3 cm (1 ft)
Back 60.6 cm (2 ft)
Power requirements