Aiko CTH3-200 Cassette Player User Manual


 
CTH3-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
18 of 71
Step 6.3.2 Coupling and Tube Assembly (Continued)
Step 6.4 Turbulator Installation
10' ± 1'
(3 m ± .25 m)
Total Overall
Tube Length
7' 6" ± 1'
(2.3 m ± .25 m)
Model
Tube Length
Minimum
CTH3-80 20' (6 m)
CTH3-115 30' (9 m)
CTH3-150 40' (12 m)
CTH3-200 50' (15 m)
T
w
i
s
t
Pull String
Tab
Fold tab around outside
of tube nearest to the vent to
hold turbulator in place.
Turbulator
Section
Turbulator
Adapter
Description Part Number
Turbulator Adapter 03051503
Turbulator Section 03051504
Tube 91409XXX
Turbulator Installation
CTH3-80 2nd 10' Section
CTH3-115 3rd 10' Section
CTH3-150 4th 10' Section
CTH3-200 N/A
Tu rbulator must be installed in
the last standard section of
tube. Turbulator is not required
on the CTH3-200.